Technical Specifications
| Input Voltage |
400 V / 480V +/-10% 3 phase 4 wire |
| Power factor |
0.98 |
| Frequency |
50/60 Hz +/-1,5 -4% (adjustable) |
| Starting current |
0,1% x l nom |
| Ride Through time |
15 sec. 100% load |
| - |
30 sec. half load (longer time at request) |
| Voltage (static) |
+/-1% |
| Voltage (dynamic) |
+/-5% |
| Recovery time |
250ms 1000 ms |
| Voltage THD |
3.5% (phase-phase with linear load) |
| Frequency |
according to mains input frequency |
| Voltage symmetry |
120 +/-1% |
| Fault clearing capacity |
>10 x l nom |
| Flywheel speed all types |
max 2900 rpm |
| Efficiency |
up to 96% |
| Cable entry |
bottom entry (optional top entry) |
| Ambient temperature |
5 graden celsius - 40 graden celcius |
| Altitude |
max 3000 m without power de-rating |
| Degree of protection |
IP21 |
| Classification |
G3 acc. to IEC 88528-11 |
Data for the containerised Ride Through systems or specific requirements are available at request. All data is for information and is subjected to change without prior notice. No rights can be obtained from the content of this page. Data provided in our offerings prevail at all times.
|
|